Conductive Point level switch Nivotester FTW325

Conductive Point level switch Nivotester FTW325

Category:Level
Information

Information

Point level switch with intrinsically safe signal circuit for connection to a conductive sensor

For point level detection in tanks for liquids also for hazardous areas. Overfill prevention for tanks with flammable or non-flammable water-polluting liquids. Pump dry running protection.

Mounting: Standard rails in cabinet

Two-point control and point level detection

Ambient temperature: -20 to +60°C (-4 to +140°F)

International explosion protection certificates

Cost-effective point level switch for conductive liquids

Intrinsically safe signal circuit EEx ia IIC for using sensors in hazardous areas

Line monitoring up to the sensor

Configurable sensitivity range

Alarm relay can be switched as second level relay (SPDT)

Easy wiring thanks to pluggable terminal blocks

Specifications

Min. density of medium
min. 10 uS
Measuring principle
Conductive
Characteristic / Application
2-channel level measurement device, level limit, switch delay, two-point control
Supply / Communication
85V ... 253V AC 20V ... 30V AC 20V ... 60V DC
Ambient temperature
-20 °C ... 60 °C (-4 °F ... 140 °F)
Min. density of medium
min. 10 uS
Communication
2 relays SPDT/DPDT
Certificates / Approvals
ATEX, FM, CSA, NEPSI, EAC
Safety approvals
Overfill protection WHG