Micropilot FMR62B – 80 GHz radar sensor

Micropilot FMR62B – 80 GHz radar sensor

Category:Level
Information

Information

Smart Safety for your process

The Micropilot FMR62B is suitable for free-space applications up to 80m and offers high beam focusing for vessels with many internal fittings.

Process connections: Flanges

Temperature: –196 to +450 °C (-320 to +842°F)

Pressure: –1 bis +160 bar (-14.5 to 2320.6 psi)

Maximum measuring range: 80 m (262.5 ft)

Accuracy: ±1 mm (0.04 in)

W-band: 80 GHz

International explosion protection certificates, overfill prevention WHG, SIL, marine approval, 5- or 10-point factory calibration certificate

Increased productivity thanks to process monitoring, verification, and diagnostics in the running process with Heartbeat Technology

Safety by design: Device development according to IEC 61508 for SIL 2 and SIL 3 applications (e.g. in homogeneous redundancy)

Reduction of systematic errors through guided SIL-locking, verification and proof testing

Easy handling through intuitive operation and wizards, for commissioning and verifications

Easier troubleshooting through recommended actions shown on the display

The new generation 80 GHz radar sensors

Foam detection with Heartbeat Technology

Specifications

Accuracy
+/-1 mm (0.04 in)
Process temperature
-196 … +450 °C (-321 … +842 °F)
Process pressure / max. overpressure limit
Vacuum...160 bar (2320 psi)
Max. measurement distance
80 m (262 ft)
Main wetted parts
316L or PTFE (clad 316L flanges)
Measuring principle
Level radar
Characteristic / Application
Premium device for continuous non-contact level measurements, where aggressive media are used; For vessels with many internals
Specialities
Heartbeat Technology; SIL 2/3 according to IEC 61508; Bluetooth® commissioning; Operation and maintenance with SmartBlue App; HistoROM; RFID TAG for easy identification; Very narrow beam angle
Supply / Communication
2-wire (HART/ PROFIBUS PA) PROFINET with Ethernet-APL Bluetooth® wireless technology
Frequency
W-Band (~80 GHz)
Accuracy
+/-1 mm (0.04 in)
Ambient temperature
-40 … +85 °C (-40 … +185 °F)
Process temperature
-196 … +450 °C (-321 … +842 °F)
Process pressure / max. overpressure limit
Vacuum...160 bar (2320 psi)
Main wetted parts
316L or PTFE (clad 316L flanges)
Process connection
Flange: DN50 ... DN150 ASME 2" ... 8"
Max. measurement distance
80 m (262 ft)
Communication
4...20 mA HART Additional analog or switch output PROFIBUS PA PROFINET with Ethernet-APL Bluetooth® wireless technology and app (optional)
Certificates / Approvals
IEC Ex, ATEX, CSA C/US, EAC Ex, JPN Ex, KC Ex, INMETRO Ex, NEPSI Ex, UK Ex
Safety approvals
Overfill protection WHG; SIL 2/ SIL 3
Design approvals
Acceptance test certificate 3.1, EN10204; NACE MR0175 / ISO 15156; NACE MR0103 / ISO 17945; Declaration of Conformity ASME B31.3; Conformity to cGMP; AD2000; PMI test; CRN approval; Helium leak test; Liquid penetrant test AD2000-HP5-3(PT); Liquid penetrant testing ISO23277-1 (PT); Liquid penetrant testing ASME VIII-1 (PT); Welding documentation (according to ISO or ASME)
Hygienic approvals
EU Food Contact Material (EC) 1935/2004; US Food Contact Material FDA CFR 21
Marine approval
ABS, LR, BV, RINA, DNV
Options
Display, Customized settings, App 'SmartBlue' for commissioning and operation via Bluetooth Gas-tight implementation; Overvoltage protection; PWIS free
Application limits
Strong turbulences and foam, long stilling wells (>12 m) and bypass -> FMR5x,FMP5x