Digital free chlorine sensor Memosens CCS51E

Digital free chlorine sensor Memosens CCS51E

Категория:Liquid analysis
Информация

Информация

Memosens sensor for drinking water, pool and process water as well as utilities in all industries

Memosens CCS51E free chlorine sensor

Free chlorine sensor CCS51E in Flowfit CYA27 assembly

The free chlorine sensor Memosens CCS51E is suitable for a wide range of water qualities:

Drinking water: to secure disinfection

Utilities: to detect free chlorine and avoid any damage

Process water: for hygienic and safe packaging and bottling of products in food processing

Pool water: to dose disinfectant efficiently

The low-maintenance, amperometric sensor reduces the cost of ownership of the measuring point, particularly compared to colorimetric measuring systems.

Increased process up-time: pre-calibration of the sensor allows for real plug & play and faster polarization time thanks to Memosens 2.0 technology.

Fast response time (t 90 < 25 s) provides an accurate process view and enables prompt reaction to process changes as well as efficient process control.

High process safety and efficient dosing: precise and long-term stable measurement ensures consistent process monitoring and permits individually adapted disinfectant dosing.

Suitable sensor versions for every measurement range: From trace measurement up to free chlorine concentrations of 200 mg/l.

Connection to the Liquiline multiparameter transmitter facilitates easy combination with other parameters of liquid analysis such as pH and ORP.

Disinfection is everywhere - and the digital free chlorine sensor Memosens CCS51E helps you with it

Документация

Спецификации

Measuring range
Trace: 0 to 5 mg/l HOCl Standard: 0 to 20 mg/l HOCl High: 0 to 200 mg/l HOCl
Process temperature
0 to 55 °C (32 to 130 °F), non-freezing
Process pressure
Max. 1 bar (max. 14.5 psi)
Measuring method
Closed, membrane covered measuring cell Reduction of free chlorine at the cathode
Measuring principle
Free chlorine
Application
Ensuring reliable disinfection in drinking water Process water Dosing disinfectant efficiently in pool water Detect the absence or presence of free chlorine in Utilities Guarantee food safety and provide hygienic packaging and bottling
Characteristic
Amperometric measurement of dissolved free chlorine
Measuring range
Trace: 0 to 5 mg/l HOCl Standard: 0 to 20 mg/l HOCl High: 0 to 200 mg/l HOCl
Measuring method
Closed, membrane covered measuring cell Reduction of free chlorine at the cathode
Design
Closed amperometric 2-electrode measuring cell with PVDF membrane
Material
Sensor shaft: POM Membrane: PVDF Membrane cap: PVDF Sealing ring: FKM
Dimension
Diameter: 25 mm (0.98 inch) Length: 161 mm (6.34 inch)
Process temperature
0 to 55 °C (32 to 130 °F), non-freezing
Process pressure
Max. 1 bar (max. 14.5 psi)
Temperature sensor
10k NTC integrated (Memosens)
Connection
Inductive, digital connection head with Memosens