EngyCal RH33 BTU meter

EngyCal RH33 BTU meter

Категория:System products
Информация

Информация

Calibratable BTU meter for one measuring point with one pulse/analog input for flow and two RTD/analog inputs for temperature/pressure

Recording and billing the quantities of heat and cold in:

Heating circuits

Cooling circuits

Combined heating and cooling circuits

Typical application areas in industry, long-distance heat networks and building automation.

Transparent energy consumption helps you save on energy costs

Calibrated, electronically paired temperature sensors ensure the highest accuracy and enable replacement of individual temperature sensors even for certified devices in the field (without reapproval!)

Tariff counter for requirements-based billing

Detailed data logging of current and counter values and of error messages, off-limit conditions and changes to operating parameters

Standard models are suitable for connecting and supplying all common volume flow transmitters and temperature measuring points

Remote readout via Ethernet and fieldbuses

Verified and certified reliability and accuracy

Документация

Спецификации

Input
1x Puls/Analog 2x RTD/Analog Loop power supply 24V DC (+/-16%)
Output
1x 4...20mA 2x digital (Open Collector)
Display
160 x 80 Dot-Matrix LCD with white backlit colour change in case of alarm event active display area 70 x 34 mm
Calculations
heat quantity and heat quantity difference
Measuring principle
Energy manager
Measuring principle
Energy manager
Function
Monitoring and billing of energy in heating and cooling applications as well as combined heating-and cooling circles. Typical applications can be found in industries, district heating and building automation.
Calculations
heat quantity and heat quantity difference
Number of applications
1
Calculation standards
IAPWS-97
Communication
web server USB Ethernet Modbus RTU/TCP Slave M-Bus
Power supply
Not defined
Loop power supply
Low voltage power supply: 100 bis 230 V AC (-15% / +10%) Small voltage power supply: 24 V DC (-50% / +75%) 24 V AC (±50%)
Protection class
IP65
Input
1x Puls/Analog 2x RTD/Analog Loop power supply 24V DC (+/-16%)
Output
1x 4...20mA 2x digital (Open Collector)
Dimensions (WxHxD)
144 x 144 x 103.1 mm (5.67" x 5.67" x 4.06")
Operation
3 button on site or via FieldCare read out of historical / logged data via Field Data Manager Software (SQL database and visualization interface) selectable language
Display
160 x 80 Dot-Matrix LCD with white backlit colour change in case of alarm event active display area 70 x 34 mm
Software functions
Calculated Values: Energy, volume, density, enthalpy & enthalpy difference, DP-Flow-Compensation, mass, temperature difference Counters: Volume, mass, energy, counter in case of failure Optional: tariff 1, tariff 2 or seperated heating energy, cooling energy, bilance energy
Certificates
CSA GP MID 004 (custody transfer) according EN1434 (water/other liquids) OIML R75
Measuring principle
Energy manager
Function
Monitoring and billing of energy in heating and cooling applications as well as combined heating-and cooling circles. Typical applications can be found in industries, district heating and building automation.
Certification
CE, UL listed, CSA GP, MID 004 (custody transfer) according EN1434 (water/other liquids) and OIML R75
Input
1x Puls/Analog, 2x RTD/Analog, Loop power supply 24V DC (+/-16%)
Output
1x 4...20mA, 2x digital (Open Collector)
Relay output
2x
Auxiliary power supply
Low voltage power supply: 100 bis 230 V AC (-15% / +10%); Small voltage power supply: 24 V DC (-50% / +75%), 24 V AC (±50%)
Dimensions (wxhxd)
144 x 144 x 103.1 mm (5.67" x 5.67" x 4.06")
Software
Calculated Values: Energy, volume, density, enthalpy & enthalpy difference, DP-Flow-Compensation, mass, temperature difference; Counters: volume, mass, energy, counter in case of failure Optional: tariff 1, tariff 2 or seperated heating energy, cooling energy, bilance energy
Operation
3 button on site or via FieldCare; read out of historical / logged data via Field Data Manager Software (SQL database and visualization interface), selectable language
Display
160 x 80 Dot-Matrix LCD with white backlit, colour change in case of alarm event, active display area 70 x 34 mm
Others
electronic temperature sensor matching via CvD coefficients, logbook measured values, custody transfer logbook, event logbook, limit monitoring
Calculations
IAPWS-IF97